Deterioration of service reservoirs due to soft water attack
Service reservoirs in the UK designed in accordance with EN 206 have shown deterioration due to soft water attack, which is a form of mild acid attack, within one year of commissioning. The attack is represented by aggressive water transforming the surface into a soft paste fully depleted of calcium...