Calculation of Last Current Loop Parameters and TRV Parameters in T100a Breaking Test of High Voltage Circuit-breakers

Asymmetric short-circuit fault breaking test T100a is an important test item of High-voltage AC Circuit-breakers. In non-effectively earthed neutral system the first pole to clear factor is 1.5 and the transient recovery voltage (TRV) has two or four parameters. By establishing the expression of sho...

Full description

Saved in:
Bibliographic Details
Main Authors: HE Ninghui, WAN Hua, XUE Fei, WU Hui, ZHANG Pei, MA Kui
Format: Article
Language:zho
Published: Harbin University of Science and Technology Publications 2023-06-01
Series:Journal of Harbin University of Science and Technology
Subjects:
Online Access:https://hlgxb.hrbust.edu.cn/#/digest?ArticleID=2215
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Asymmetric short-circuit fault breaking test T100a is an important test item of High-voltage AC Circuit-breakers. In non-effectively earthed neutral system the first pole to clear factor is 1.5 and the transient recovery voltage (TRV) has two or four parameters. By establishing the expression of short-circuit current and voltage in T100a breaking test, the last current loop parameters and TRV parameters are analyzed and calculated in major loop and extended major loop. Finally, the last current loop parameters and TRV parameters are calculated by taking T100a interruption test of rated voltage 40. 5 kV and rated voltage 126 kV Circuit-breakers as examples, which provide an assessment basis for the breaking test of circuit breakers.
ISSN:1007-2683