Calculation Model of Thermodynamic Properties of Saturated Liquid for HFC-32 Refrigerant

Simple and effective calculation models to determine thermodynamic properties of refrigerant are very necessary for simulation of refrigeration system. Correlations of saturated vapor pressure and liquid density for HFC-32 refrigerant were presented. On basis of GMA state equation of liquid for HFC-...

Full description

Saved in:
Bibliographic Details
Main Authors: Tian Zhen, Gu Bo, Wang Ting, Hao Yuancheng
Format: Article
Language:zho
Published: Journal of Refrigeration Magazines Agency Co., Ltd. 2013-01-01
Series:Zhileng xuebao
Subjects:
Online Access:http://www.zhilengxuebao.com/thesisDetails#10.3969/j.issn.0253-4339.2013.02.028
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Simple and effective calculation models to determine thermodynamic properties of refrigerant are very necessary for simulation of refrigeration system. Correlations of saturated vapor pressure and liquid density for HFC-32 refrigerant were presented. On basis of GMA state equation of liquid for HFC-32, Helmholtz bias function and Maxwell relationship of the thermal physical parameters, the calculation models of enthalpy, entropy and specific heat capacity were deduced. The calculation models mentioned above with no iteration can achieve high precision and stability. Comparisons between calculation models and REFPROP7 , covering saturation liquid line(275~335 ,0.862~4.095 ), have been made. The results show that, the average relative error and maximum relative error for all calculation models are less than 0.776% and 4.464%, respectively.
ISSN:0253-4339