Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy

Faults of heating, ventilation, and air-conditioning (HVAC) systems can cause significant consequences, such as negatively affecting thermal comfort of occupants, energy demand, indoor air quality, etc. Several methods of fault detection and diagnosis (FDD) in building energy systems have been propo...

Full description

Saved in:
Bibliographic Details
Main Authors: Antonio Rosato, Mohammad El Youssef, Rita Mercuri, Armin Hooman, Marco Savino Piscitelli, Alfonso Capozzoli
Format: Article
Language:English
Published: MDPI AG 2025-01-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/18/3/618
Tags: Add Tag
No Tags, Be the first to tag this record!
_version_ 1850200111086305280
author Antonio Rosato
Mohammad El Youssef
Rita Mercuri
Armin Hooman
Marco Savino Piscitelli
Alfonso Capozzoli
author_facet Antonio Rosato
Mohammad El Youssef
Rita Mercuri
Armin Hooman
Marco Savino Piscitelli
Alfonso Capozzoli
author_sort Antonio Rosato
collection DOAJ
description Faults of heating, ventilation, and air-conditioning (HVAC) systems can cause significant consequences, such as negatively affecting thermal comfort of occupants, energy demand, indoor air quality, etc. Several methods of fault detection and diagnosis (FDD) in building energy systems have been proposed since the late 1980s in order to reduce the consequences of faults in heating, ventilation, and air-conditioning (HVAC) systems. All the proposed FDD methods require laboratory data, or simulated data, or field data. Furthermore, the majority of the recently proposed FDD methods require labelled faulty and normal data to be developed. Thus, providing reliable ground truth data of HVAC systems with different technical characteristics is of great importance for advances in FDD methods for HVAC units. The primary objective of this study is to examine the operational behaviour of a typical single-duct dual-fan constant air volume air-handling unit (AHU) in both faulty and fault-free conditions. The investigation encompasses a series of experiments conducted under Mediterranean climatic conditions in southern Italy during summer and winter. This study investigates the performance of the AHU by artificially introducing seven distinct typical faults: (1) return air damper kept always closed (stuck at 0%); (2) fresh air damper kept always closed (stuck at 0%); (3) fresh air damper kept always opened (stuck at 100%); (4) exhaust air damper kept always closed (stuck at 0%); (5) supply air filter partially clogged at 50%; (6) fresh air filter partially clogged at 50%; and (7) return air filter partially clogged at 50%. The collected data from the faulty scenarios are compared to the corresponding data obtained from fault-free performance measurements conducted under similar boundary conditions. Indoor thermo-hygrometric conditions, electrical power and energy consumption, operation time of AHU components, and all key operating parameters are measured for all the aforementioned faulty tests and their corresponding normal tests. In particular, the experimental results demonstrated that the exhaust air damper stuck at 0% significantly reduces the percentage of time with indoor air relative humidity kept within the defined deadbands by about 29% (together with a reduction in the percentage of time with indoor air temperature kept within the defined deadbands by 7.2%) and increases electric energy consumption by about 13% during winter. Moreover, the measured data underlined that the effects on electrical energy demand and indoor thermo-hygrometric conditions are minimal (with deviations not exceeding 5.6% during both summer and winter) in the cases of 50% clogging of supply air filter, fresh air filter, and return air filter. The results of this study can be exploited by researchers, facility managers, and building operators to better recognize root causes of faulty evidences in AHUs and also to develop and test new FDD tools.
format Article
id doaj-art-e9b59c27384e48f1b489d451f82d26d7
institution OA Journals
issn 1996-1073
language English
publishDate 2025-01-01
publisher MDPI AG
record_format Article
series Energies
spelling doaj-art-e9b59c27384e48f1b489d451f82d26d72025-08-20T02:12:25ZengMDPI AGEnergies1996-10732025-01-0118361810.3390/en18030618Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern ItalyAntonio Rosato0Mohammad El Youssef1Rita Mercuri2Armin Hooman3Marco Savino Piscitelli4Alfonso Capozzoli5Department of Architecture and Industrial Design, SENS i-Lab, University of Campania Luigi Vanvitelli, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, SENS i-Lab, University of Campania Luigi Vanvitelli, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, SENS i-Lab, University of Campania Luigi Vanvitelli, 81031 Aversa, ItalyDepartment of Energy “Galileo Ferraris”, Politecnico di Torino, 10129 Turin, ItalyDepartment of Energy “Galileo Ferraris”, Politecnico di Torino, 10129 Turin, ItalyDepartment of Energy “Galileo Ferraris”, Politecnico di Torino, 10129 Turin, ItalyFaults of heating, ventilation, and air-conditioning (HVAC) systems can cause significant consequences, such as negatively affecting thermal comfort of occupants, energy demand, indoor air quality, etc. Several methods of fault detection and diagnosis (FDD) in building energy systems have been proposed since the late 1980s in order to reduce the consequences of faults in heating, ventilation, and air-conditioning (HVAC) systems. All the proposed FDD methods require laboratory data, or simulated data, or field data. Furthermore, the majority of the recently proposed FDD methods require labelled faulty and normal data to be developed. Thus, providing reliable ground truth data of HVAC systems with different technical characteristics is of great importance for advances in FDD methods for HVAC units. The primary objective of this study is to examine the operational behaviour of a typical single-duct dual-fan constant air volume air-handling unit (AHU) in both faulty and fault-free conditions. The investigation encompasses a series of experiments conducted under Mediterranean climatic conditions in southern Italy during summer and winter. This study investigates the performance of the AHU by artificially introducing seven distinct typical faults: (1) return air damper kept always closed (stuck at 0%); (2) fresh air damper kept always closed (stuck at 0%); (3) fresh air damper kept always opened (stuck at 100%); (4) exhaust air damper kept always closed (stuck at 0%); (5) supply air filter partially clogged at 50%; (6) fresh air filter partially clogged at 50%; and (7) return air filter partially clogged at 50%. The collected data from the faulty scenarios are compared to the corresponding data obtained from fault-free performance measurements conducted under similar boundary conditions. Indoor thermo-hygrometric conditions, electrical power and energy consumption, operation time of AHU components, and all key operating parameters are measured for all the aforementioned faulty tests and their corresponding normal tests. In particular, the experimental results demonstrated that the exhaust air damper stuck at 0% significantly reduces the percentage of time with indoor air relative humidity kept within the defined deadbands by about 29% (together with a reduction in the percentage of time with indoor air temperature kept within the defined deadbands by 7.2%) and increases electric energy consumption by about 13% during winter. Moreover, the measured data underlined that the effects on electrical energy demand and indoor thermo-hygrometric conditions are minimal (with deviations not exceeding 5.6% during both summer and winter) in the cases of 50% clogging of supply air filter, fresh air filter, and return air filter. The results of this study can be exploited by researchers, facility managers, and building operators to better recognize root causes of faulty evidences in AHUs and also to develop and test new FDD tools.https://www.mdpi.com/1996-1073/18/3/618air-handling unitdamper faultfilter faultfault detection and diagnosisfault impact assessmentenergy management
spellingShingle Antonio Rosato
Mohammad El Youssef
Rita Mercuri
Armin Hooman
Marco Savino Piscitelli
Alfonso Capozzoli
Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
Energies
air-handling unit
damper fault
filter fault
fault detection and diagnosis
fault impact assessment
energy management
title Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
title_full Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
title_fullStr Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
title_full_unstemmed Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
title_short Assessment of Indoor Thermo-Hygrometric Conditions and Energy Demands Associated to Filters and Dampers Faults via Experimental Tests of a Typical Air-Handling Unit During Summer and Winter in Southern Italy
title_sort assessment of indoor thermo hygrometric conditions and energy demands associated to filters and dampers faults via experimental tests of a typical air handling unit during summer and winter in southern italy
topic air-handling unit
damper fault
filter fault
fault detection and diagnosis
fault impact assessment
energy management
url https://www.mdpi.com/1996-1073/18/3/618
work_keys_str_mv AT antoniorosato assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly
AT mohammadelyoussef assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly
AT ritamercuri assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly
AT arminhooman assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly
AT marcosavinopiscitelli assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly
AT alfonsocapozzoli assessmentofindoorthermohygrometricconditionsandenergydemandsassociatedtofiltersanddampersfaultsviaexperimentaltestsofatypicalairhandlingunitduringsummerandwinterinsouthernitaly