A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network

This study proposed a modified passive islanding technique that combines over/under frequency (OUF), rate of change of frequency (ROCOF), rate of change of phase angle difference (ROCPAD), and rate of change of voltage (ROCOV) for sensing of islanding and nonislanding conditions. The technique was i...

Full description

Saved in:
Bibliographic Details
Main Authors: Bemdoo Saka, Jacob Tsado, Vedat Kiray, Suleiman Usman Hussein
Format: Article
Language:English
Published: Wiley 2025-01-01
Series:International Transactions on Electrical Energy Systems
Online Access:http://dx.doi.org/10.1155/etep/7693707
Tags: Add Tag
No Tags, Be the first to tag this record!
_version_ 1850241574782369792
author Bemdoo Saka
Jacob Tsado
Vedat Kiray
Suleiman Usman Hussein
author_facet Bemdoo Saka
Jacob Tsado
Vedat Kiray
Suleiman Usman Hussein
author_sort Bemdoo Saka
collection DOAJ
description This study proposed a modified passive islanding technique that combines over/under frequency (OUF), rate of change of frequency (ROCOF), rate of change of phase angle difference (ROCPAD), and rate of change of voltage (ROCOV) for sensing of islanding and nonislanding conditions. The technique was implemented in MATLAB/Simulink and applied to the distribution network of the Federal Capital Territory (FCT) of Nigeria containing 120 buses to maintain a stable power supply to its critical loads during grid outages. The method utilized the frequency, voltage, and current signals as input to the combined method. For each of the relays, the low threshold was for a fast operation while the high threshold was for a secure operation. First, the OUF, ROCOF, ROCOV, and ROCPAD relays were combined using an AND gate to limit the relay operation during short circuits since the ROCOV measures the voltage drop and determines whether it is in grid-connected or islanding mode. After that, the higher set threshold of the ROCOF was connected using a logical OR gate to limit the operation of the relay under transients and noises. Finally, the higher set threshold of the ROCPAD was used to sense islanding in case the lower threshold failed to initially detect it. The efficacy of the technique was tested on the FCT distribution network, and the result showed successful islanding for the loss of the grid supply and loss of power supply due to fault on the 330 kV line, while the loss of 33 kV feeder and loss of power supply at a single supply point were nonislanding events. After islanding due to an outage and loss of the 330 kV line, it took 0.01138 and 0.000316 s to switch to the DES, and the optimal capacities that supplied power to the critical loads were 33.2 MW at Bus 13, 18.9 MW at Bus 120, 48.4 MW at Bus 72, and 45.1 MW at Bus 46. The total connection of the DES was able to supply 144.8 MW out of the total peak load of 600 MW which represents about 24.13% of the total system load referred to as the critical loads. Therefore, connecting DES capable of islanding operation to the distribution network improves power supply security, supply continuity to consumers, and customer satisfaction.
format Article
id doaj-art-dcdffd9674ec42fba4f383819ae35d19
institution OA Journals
issn 2050-7038
language English
publishDate 2025-01-01
publisher Wiley
record_format Article
series International Transactions on Electrical Energy Systems
spelling doaj-art-dcdffd9674ec42fba4f383819ae35d192025-08-20T02:00:34ZengWileyInternational Transactions on Electrical Energy Systems2050-70382025-01-01202510.1155/etep/7693707A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution NetworkBemdoo Saka0Jacob Tsado1Vedat Kiray2Suleiman Usman Hussein3Electrical and Electronics Engineering DepartmentElectrical and Electronics Engineering DepartmentElectrical and Electronics Engineering DepartmentElectrical and Electronics Engineering DepartmentThis study proposed a modified passive islanding technique that combines over/under frequency (OUF), rate of change of frequency (ROCOF), rate of change of phase angle difference (ROCPAD), and rate of change of voltage (ROCOV) for sensing of islanding and nonislanding conditions. The technique was implemented in MATLAB/Simulink and applied to the distribution network of the Federal Capital Territory (FCT) of Nigeria containing 120 buses to maintain a stable power supply to its critical loads during grid outages. The method utilized the frequency, voltage, and current signals as input to the combined method. For each of the relays, the low threshold was for a fast operation while the high threshold was for a secure operation. First, the OUF, ROCOF, ROCOV, and ROCPAD relays were combined using an AND gate to limit the relay operation during short circuits since the ROCOV measures the voltage drop and determines whether it is in grid-connected or islanding mode. After that, the higher set threshold of the ROCOF was connected using a logical OR gate to limit the operation of the relay under transients and noises. Finally, the higher set threshold of the ROCPAD was used to sense islanding in case the lower threshold failed to initially detect it. The efficacy of the technique was tested on the FCT distribution network, and the result showed successful islanding for the loss of the grid supply and loss of power supply due to fault on the 330 kV line, while the loss of 33 kV feeder and loss of power supply at a single supply point were nonislanding events. After islanding due to an outage and loss of the 330 kV line, it took 0.01138 and 0.000316 s to switch to the DES, and the optimal capacities that supplied power to the critical loads were 33.2 MW at Bus 13, 18.9 MW at Bus 120, 48.4 MW at Bus 72, and 45.1 MW at Bus 46. The total connection of the DES was able to supply 144.8 MW out of the total peak load of 600 MW which represents about 24.13% of the total system load referred to as the critical loads. Therefore, connecting DES capable of islanding operation to the distribution network improves power supply security, supply continuity to consumers, and customer satisfaction.http://dx.doi.org/10.1155/etep/7693707
spellingShingle Bemdoo Saka
Jacob Tsado
Vedat Kiray
Suleiman Usman Hussein
A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
International Transactions on Electrical Energy Systems
title A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
title_full A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
title_fullStr A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
title_full_unstemmed A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
title_short A Passive Islanding Method to Improve the Stability of Power Supply to Critical Loads in a Real Distribution Network
title_sort passive islanding method to improve the stability of power supply to critical loads in a real distribution network
url http://dx.doi.org/10.1155/etep/7693707
work_keys_str_mv AT bemdoosaka apassiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT jacobtsado apassiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT vedatkiray apassiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT suleimanusmanhussein apassiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT bemdoosaka passiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT jacobtsado passiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT vedatkiray passiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork
AT suleimanusmanhussein passiveislandingmethodtoimprovethestabilityofpowersupplytocriticalloadsinarealdistributionnetwork