A Novel Controllable Reactor Technology for Reactive Power Compensation of Electrified Railways

A multi-winding reactor, the secondary windings of which connecting anti-parallel thyristors and voltage- source inverter (VSI) respectively, can obtain reactance varying in a wide range continuously with the thyristors′ stepping switching and VSI controlling. With parallel operation of the controll...

Full description

Saved in:
Bibliographic Details
Main Authors: 张宇, 李江红, 陈乔夫, 王坚, 谭娟
Format: Article
Language:zho
Published: Editorial Office of Control and Information Technology 2010-01-01
Series:Kongzhi Yu Xinxi Jishu
Subjects:
Online Access:http://ctet.csrzic.com/thesisDetails#10.13889/j.issn.2095-3631.2010.05.005
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A multi-winding reactor, the secondary windings of which connecting anti-parallel thyristors and voltage- source inverter (VSI) respectively, can obtain reactance varying in a wide range continuously with the thyristors′ stepping switching and VSI controlling. With parallel operation of the controllable reactor and fixed capacitor branches, reactive power of traction substations can be regulated automatically according to dynamic loading for increasing power factor. Simulating and experimental results validate the advantages of the presented reactor such as fast response, high compensating precision and low harmonic output etc.
ISSN:2096-5427