Study on the Capability of a Two Phase Natural Convection System for Hot-swappable Communication Cabinets
Based on the two phase natural convection, a system with R22 for the hot-swappable communication cabinet is built and tested for its heat dissipation capability. The result shows that this system can handle more than 3000W with the cooling water at about 28℃, meanwhile, it keeps the temperature of t...
Saved in:
| Main Authors: | , , , , , , |
|---|---|
| Format: | Article |
| Language: | zho |
| Published: |
Journal of Refrigeration Magazines Agency Co., Ltd.
2012-01-01
|
| Series: | Zhileng xuebao |
| Subjects: | |
| Online Access: | http://www.zhilengxuebao.com/thesisDetails#10.3969/j.issn.0253-4339.2012.01.041 |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
| Summary: | Based on the two phase natural convection, a system with R22 for the hot-swappable communication cabinet is built and tested for its heat dissipation capability. The result shows that this system can handle more than 3000W with the cooling water at about 28℃, meanwhile, it keeps the temperature of the electronic module to be lower than 65℃. Moreover, the tests of unbalance heat load start up and varying during operation are carried out to simulate cases of the heat load changing and hot swapping in a real cabinet. The result tells that the system operates stable with unbalance heat load and meets the requirement for hot swapping. |
|---|---|