Performance Analysis of a Novel Temperature and Humidity Independent Control System under Winter Conditions

Temperature and humidity independent control systems handle sensible load and latent load separately. They are usually more efficient and consume less energy than traditional air conditioning systems. In this paper, a novel humidity control system (DESICA), and the temperature and humidity independe...

Full description

Saved in:
Bibliographic Details
Main Authors: Huang Yi, Jiang Yu, Ge Tianshu, Wang Ruzhu
Format: Article
Language:zho
Published: Journal of Refrigeration Magazines Agency Co., Ltd. 2014-01-01
Series:Zhileng xuebao
Subjects:
Online Access:http://www.zhilengxuebao.com/thesisDetails#10.3969/j.issn.0253-4339.2014.02.087
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Temperature and humidity independent control systems handle sensible load and latent load separately. They are usually more efficient and consume less energy than traditional air conditioning systems. In this paper, a novel humidity control system (DESICA), and the temperature and humidity independent control system constituted of DESICA and VRV (variable refrigerant volume air conditioning system), are studied through field experiment under winter conditions. Comparisons have been made to common adopted joint heat recovery ventilator (HRV) and VRV system. The results show that DESICA&VRV system provides more indoor thermal comfort (21℃, 50%) and consumes 9% less energy than HRV&VRV system.