IMPROVEMENT OF TRANSIENT STABILITY OF AUTONOMOUS POWER SYSTEM ON BASIS OF WIDE AREA CONTROL SYSTEM

Abstract: The coordinated generation and load control to increase transient stability level of oil- production enterprise autonomous power system with dominant motor load is studied in the paper. Mutual angle between voltage phasors at gas turbine plant bus and equivalent load node as well as slip d...

Full description

Saved in:
Bibliographic Details
Main Authors: A. Yu. Stogov, A. N. Belyaev
Format: Article
Language:English
Published: Kazan State Power Engineering University 2019-04-01
Series:Известия высших учебных заведений: Проблемы энергетики
Subjects:
Online Access:https://www.energyret.ru/jour/article/view/869
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Abstract: The coordinated generation and load control to increase transient stability level of oil- production enterprise autonomous power system with dominant motor load is studied in the paper. Mutual angle between voltage phasors at gas turbine plant bus and equivalent load node as well as slip difference of synchronous machines are used as input signals. It is shown that implementation of additional control allows to increase the level of transient stability by more than 40%. The combined coordination of power system stabilizer of synchronous generators and motors as well as gas turbine frequency control parameters is applied. The positive impact of power system stabilizer settings on post-accident conditions is proved by analysis of small signal stability.