Unified Power Quality Controller Based on Synchronous Rotating Coordinates

In order to improve the control precision and response speed of UPQC, it presented a novel method for three-phase current harmonics and single-phase voltage sag detection based on the synchronous rotating coordinates. The controller detectes the voltage and current compensation instructions, and the...

Full description

Saved in:
Bibliographic Details
Main Authors: LIU Huadong, JIAO Yuefeng, DENG Ming
Format: Article
Language:zho
Published: Editorial Office of Control and Information Technology 2015-01-01
Series:Kongzhi Yu Xinxi Jishu
Subjects:
Online Access:http://ctet.csrzic.com/thesisDetails#10.13889/j.issn.2095-3631.2015.04.008
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In order to improve the control precision and response speed of UPQC, it presented a novel method for three-phase current harmonics and single-phase voltage sag detection based on the synchronous rotating coordinates. The controller detectes the voltage and current compensation instructions, and then combines the classical double-closed-loop control when compensating the harmonic current, and introduces the voltage current double-closed-loop control when voltage sag compensating. The prototype test results show that the response time to voltage sag suppression of the UPQC is less than 10 ms, voltage and current harmonic compensation rate is more than 90%, voltage and current THD are limited in the GB range, and the power factor maintains unity in the grid.