New Solution for Photovoltaic Station Collector Line Protection Based on Comprehensive Harmonic Drive

A new protection scheme for the collection line of photovoltaic power station based on comprehensive harmonic drive is proposed. Firstly, the harmonic sources and characteristics of the collection line fault in photovoltaic power station are analyzed, and the current harmonics are obtained by fiber...

Full description

Saved in:
Bibliographic Details
Main Authors: Jiandong WO, Wulue PAN, Yuehui LI, Jiayi WU
Format: Article
Language:zho
Published: State Grid Energy Research Institute 2025-02-01
Series:Zhongguo dianli
Subjects:
Online Access:https://www.electricpower.com.cn/CN/10.11930/j.issn.1004-9649.202404055
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A new protection scheme for the collection line of photovoltaic power station based on comprehensive harmonic drive is proposed. Firstly, the harmonic sources and characteristics of the collection line fault in photovoltaic power station are analyzed, and the current harmonics are obtained by fiber optical current transformer (FOCT), and the harmonic characteristic weight is calculated based on the nondominated sorting genetic algorithm Ⅱ (NSGA-Ⅱ) to improve the comprehensive harmonic characteristic of fault current. At the time, the high-order harmonic start-up criterion and the comprehensive harmonic action criterion are constructed. The simulation study is carried out for different fault conditions, and the effectiveness of proposed method is verified.