Experimental Research on the R134a/CO2 Cascade Refrigeration System
A test rig of the R134a/CO2 cascade supermarket refrigeration system has been built up to get a comprehensive understanding of its performance. The results show that the maximum COP of the system occurred when the condensing temperature of the CO2 cycle was about -2℃, the condensing temperature of R...
Saved in:
| Main Authors: | , , , , |
|---|---|
| Format: | Article |
| Language: | zho |
| Published: |
Journal of Refrigeration Magazines Agency Co., Ltd.
2013-01-01
|
| Series: | Zhileng xuebao |
| Subjects: | |
| Online Access: | http://www.zhilengxuebao.com/thesisDetails#10.3969/j.issn.0253-4339.2013.04.059 |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
| Summary: | A test rig of the R134a/CO2 cascade supermarket refrigeration system has been built up to get a comprehensive understanding of its performance. The results show that the maximum COP of the system occurred when the condensing temperature of the CO2 cycle was about -2℃, the condensing temperature of R134a and the evaporating temperature of CO2 was settled at 48℃ and -30℃ respectively with a temperature difference of 3℃. Moreover, the COP remained stable while the condensing temperature varied within a certain range of ±5℃. Results also show that the maximum deviation of the compressor adiabatic efficiency is within 4%, the main factor affecting the system cooling capacity is the compressor volumetric efficiency. And the performance of the cascade system could be 3% higher compared with that of conventional R404a refrigeration system at the same condition. |
|---|---|