Experimental Investigations of the Seismic Performance of a Base-Isolated Uninterruptible Power Supply (UPS) through Shaking Table Tests

Seismic performance of a UPS through shaking table tests was investigated using the input acceleration time histories with scaling factors of 50%, 100%, and 200%. The first series consists of UPS specimens supported by snip single-corner rectangular pins, and the second series consists of UPS specim...

Full description

Saved in:
Bibliographic Details
Main Authors: Gia Toai Truong, Seung-Jae Lee, Ji-Eon Lee, Kyoung-Kyu Choi
Format: Article
Language:English
Published: Wiley 2022-01-01
Series:Shock and Vibration
Online Access:http://dx.doi.org/10.1155/2022/2304290
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Seismic performance of a UPS through shaking table tests was investigated using the input acceleration time histories with scaling factors of 50%, 100%, and 200%. The first series consists of UPS specimens supported by snip single-corner rectangular pins, and the second series consists of UPS specimens supported by isolator systems. The UPS specimens in the second series significantly reduced the fundamental frequency, peak acceleration, and amplification factors but increased the damping ratio and displacement compared with those of the UPS specimens in the first series. The analytical results obtained from the analytical model agreed well with the experimental results.
ISSN:1875-9203