Study on the influence of fire source location on cable tunnel detection and alarm system

In order to study the fire detection method of cable tunnel. We carried out physical experiments in the cable tunnel test section, using the heater pyrolyze PVC so that its pyrolysis as the ignition source obtained a total of 17 fire source location points in the horizontal and vertical directions o...

Full description

Saved in:
Bibliographic Details
Main Authors: Lei Lei, Zeyu Wang, Zihao Liang
Format: Article
Language:English
Published: Elsevier 2024-12-01
Series:Case Studies in Thermal Engineering
Subjects:
Online Access:http://www.sciencedirect.com/science/article/pii/S2214157X24015387
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In order to study the fire detection method of cable tunnel. We carried out physical experiments in the cable tunnel test section, using the heater pyrolyze PVC so that its pyrolysis as the ignition source obtained a total of 17 fire source location points in the horizontal and vertical directions of seven different fire detectors, and only processed the response time data of the alarm detector obtained the response time and the analysis results were drawn. With the increase of the distance from the fire source, the response time of each type of detector increases in different forms. It is found that the detection distance of the grating fiber temperature sensor is shorter, and the response time near the fire source is more stable. The detection performance of the point pyrolytic particle detector is more affected by the detection distance, which is advantageous for the detection point to have better response performance. The intelligent active suction detector is also affected by the detection distance, which is less affected than the point detector, the response time curve is more stable, and the detection performance is better at each test point. Clc number: X Document Identification Code; A.
ISSN:2214-157X