The principle of elaboration of the relay protection against short circuits between the closely placed phases of high voltage electrical line

The article is devoted to the elaboration of the principle of relay protection against short circuits between the closely placed phases of higher voltage electrical line with self-compensation, based on the six phase’s symmetrical components. It is shown that the unsymmetrical short circuits between...

Full description

Saved in:
Bibliographic Details
Main Authors: Kiorsak M., Turcuman L., Turturica N.
Format: Article
Language:English
Published: Academy of Sciences of Moldova 2015-12-01
Series:Problems of the Regional Energetics
Subjects:
Online Access:http://journal.ie.asm.md/assets/files/08_03_29_2015.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The article is devoted to the elaboration of the principle of relay protection against short circuits between the closely placed phases of higher voltage electrical line with self-compensation, based on the six phase’s symmetrical components. It is shown that the unsymmetrical short circuits between the closely placed phases are characterized by appearance of zero and tertiary sequences of symmetrical components. This fact can be used to choose them for relay protection. The electrical basic circuits and formulas for calculation of the passive parameters of zero and tertiary filters of currents (voltages) are done. It is presented the structural-functional basic circuit scheme for relay protection against short circuits between the closely placed phases of higher voltage electrical line with self-compensation.
ISSN:1857-0070