ABOUT ACCURACY OF SYNCHRONOUS TIME IN UPS OF RUSSIA

The article presents the results of experimental studies of the accuracy of synchronous time in the Unified Power System of Russia. A description is given of experiments based on recording deviations of the clock, clocked by the voltage signal of the power network, and on the analysis of data from p...

Full description

Saved in:
Bibliographic Details
Main Authors: Y. Kononov, I. Levchenko, E. Satsuk, D. Tuchina
Format: Article
Language:Russian
Published: North Caucasus Federal University 2022-02-01
Series:Вестник Северо-Кавказского федерального университета
Subjects:
Online Access:https://vestnikskfu.elpub.ru/jour/article/view/114
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The article presents the results of experimental studies of the accuracy of synchronous time in the Unified Power System of Russia. A description is given of experiments based on recording deviations of the clock, clocked by the voltage signal of the power network, and on the analysis of data from phasor measuring unit. A constant average daily average lag of synchronous time from astronomical time of 1 s was revealed, this is due to the systematic error of frequency sensors. It is shown that even with the use of modern sensors and perfect frequency correction, the annual deviation of synchronous time can reach +9 s. The expediency of using synchronous time for monitoring instead of measuring the frequency of phase angles of voltages measured by phasor measuring unit is substantiated.
ISSN:2307-907X