Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station
This study examines an AC filter tripping incident that occurred at Lahore Converter station of ±660kV high voltage direct current (HVDC) Pak Matiari-Lahore transmission project which seriously affected the stable operation of the converter station. The fault current exceeded the trip threshold and...
Saved in:
| Main Authors: | Muhammad Imran, Abdullah Naveed, Habib Ullah, Mohammad Ahsan Shehzad, Zhang Jianmeng |
|---|---|
| Format: | Article |
| Language: | English |
| Published: |
Eldaghayes Publisher
2025-01-01
|
| Series: | Journal of Engineering Research and Reviews |
| Subjects: | |
| Online Access: | http://www.ejmanager.com/fulltextpdf.php?mno=235799 |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Similar Items
-
Multiple harmonic current injection system for AC filter capacitors in HVDC converter stations considering grid frequency fluctuation
by: Jingang Han, et al.
Published: (2025-12-01) -
Analysis on the Amplification Effect of Diode Rectifier Unbalance Input Current
by: LIU Fei, et al.
Published: (2019-01-01) -
A fault location method for internal faults of inverter in offshore wind HVDC system based on temporal characteristics of AC current
by: Shanshan Yin, et al.
Published: (2025-10-01) -
Comparative Analysis of Stability Control Strategy from Grid-connected to Island Operation Based on VSC-HVDC System
by: CHEN Qi-chao, et al.
Published: (2021-04-01) -
Hybrid AC/DC Collection and HVDC Transmission Topology for Large-scale Offshore Wind Farms
by: Wang Xiang, et al.
Published: (2025-01-01)